Consultation Hotline: 400-101-3651

Three-Phase Three-Dimensional Roll-Core Distribution Transformer


Three-dimensional roll-core distribution transformer is a kind of energy-saving power transformer. It creatively upgrades the laminated magnetic structure and three-phase layout of traditional power transformers, which optimizes the performance of transformers. The three-phase magnetic circuit is completely symmetric, with significant power-saving effect, greatly decreased noise, high heat dissipation performance, strong overload capacity, more compact structure and smaller volume.

Product introduction



Working Conditions:
No.
Conditions
Units
Parameter Values
1
Pollution Grade
 
IV
2
Ambient Temperature
Maximum Daily Temperature
40
Minimum Daily Temperature
-45
Maximum Daily Temperature Difference
K
25
Average Temperature of the Hottest Month
30
Maximum Annual Average Temperature
20
3
Humidity
Average Daily Relative Humidity
%
≤95
Average Monthly Relative Humidity
≤90
4
Altitude
m
1000
5
Solar Radiation Intensity
W/cm2
0.1
6
Maximum Icing Thickness
mm
10
7
Maximum average wind speed: keeping in good conditions for 10min at 10m from the ground level
m/s
35
8
Earthquake Resistance
Horizontal Ground Acceleration
m/s2
2
Safety Coefficient of 3 Since Resonance Cycles
 
≥1.67
9
Installation Site
 
Outdoor
Note 1: Working conditions in high altitude regions (above 1000m) must be adjusted in conformity with Q/GDW 13001-2014 (High Altitude External Insulation Configuration Technical Specification).


Product Parameters:
Table 1  30kVA ~ 1600 kVA, Three-Phase Duplex Windings, No-Load Voltage Regulation, Distribution Transformer
Rated Capacity (KV.A)
Voltage Combination & Tapping Range
Connection Symbol
No-Load Loss (kW)
On-Load Loss (kW)
No-Load Current (%)
Short-Circuit Impedance (%)
Acoustic Power Level dB(A)
High Voltage (kV)
High Voltage Tapping Range (%)
Low Voltage (kV)
30
6
6.3
10
10.5
11
±5
0.4
Dyn11
Yzn11
Yyn0
80
630/660
0.30
4.0
48
50
100
910/870
0.24
63
110
1 090/1 040
0.23
80
130
1 310/1 250
0.22
49
100
150
1 580/1 500
0.21
125
170
1 890/1 800
0.20
50
160
200
2 310/2 200
0.19
200
240
2 730/2 600
0.18
52
250
290
3 200/3 050
0.17
315
340
3 830/3 650
0.16
54
400
410
4 520/4 300
0.16
500
480
5 410/5 150
0.16
56
630
Dyn11
Yyn0
570
6 200
0.15
4.5
800
700
7 500
0.15
58
1 000
830
10 300
0.14
1 250
970
12 000
0.13
60
1 600
1 170
14 500
0.12
Note 1: If the rated capacity is 500kV.A or below, the data of “On-Load Loss” on the left of slash (/) is suitable for Dyn11 or Yzn11, on the right for Yyn0.
Note 2: Transformers with ±2×2.5% of high voltage tapping range can also be supplied upon demands.
Note 3: Transformers with 0.69kV of low voltage can also be supplied upon demands.
Note 4: Other loss values can also be used upon demands.

Address: No.1, West Xuefu Road, Longling Industrial Park, Gaoxin District, Yiyang City, Hunan Province, 413000, China

Contact No.: 0737-2222100

QQ: 3013508896

E-mail: huaxiangbyq@163.com

©2018 All Rights Reserved by Huaxiang Xiangneng Technology Co., Ltd.     湘ICP备11006305号-2